ELECTRICAL ITEMS-IV



 

6.6

EVAPORATIVE AIR COOLING SYSTEM

 

 

 

1226

ELEC-6.6.1

 

Supply and Transportation of single phase evaporative air coolingunitwithacapacityof8000CFMconsistingcabinet and water tank made of polypropylene material, blower waterpumpof40W,singlephase1.20KWmotoraxialtype fan with variable speed, 20 micron filteration, noise level less than 78 dBA with auto cleaning and water lack protectionetccomplete.Makes:CoolBreeze/BreezeAir

 

 

 

 

1

 

 

 

 

No

 

 

 

 

97800

1227

ELEC-6.6.2

Supply and Transportation of single phase evaporative air cooling unit with a capacity of 11000 - 12000 CFM consisting cabinet and water tank made of polypropylene material,blowerwaterpumpof40W,singlephase1.20KW

/ 1.5 KW motor axial type fan with variable speed, 20 micron filteration, noise level less than 78 dBA with auto cleaning and water lack protection etc complete. Makes: Cool Breeze / Breeze Air

 

 

 

 

1

 

 

 

 

No

 

 

 

 

115550

1228

ELEC-6.6.3

Supply and Transportation of three phase evaporative air cooling unit with a capacity of 17000 CFM consisting cabinet and water tank made of polypropylene material, blower water pump of 60W, three phase, 3.0 KW motor, axialtypefanwith2speed,20micronfilteration,noiselevel less than 78 dBA with auto cleaning and water lack protectionetccomplete.Makes:CoolBreeze/BreezeAir

 

 

 

 

1

 

 

 

 

No

 

 

 

 

160000

 

ELEC-6.6.4

Supply,Factoryfabrication,Transportationanderrectionof

........ guage GI sheet Rectangular ducting complete with neoprene rubber gaskets, Elbows, sheet metal / Angleiron

/ C-cleats as required, G.I.fasteners, bolts, nuts and washers, guide vanes as required, supports shall be galvanised threaded rods etc complete.

Makes : Tata / Zindal

 

 

 

1229

a

20 Guage

1

Sqft

100

1230

b

22 Guage

1

Sqft

90

1231

c

24 Guage

1

Sqft

75

 

ELEC-6.6.5

Supply,Factoryfabrication,Transportationanderrectionof

........ guage GI sheet Spiral / Round ducting complete with neoprene rubber gaskets, Elbows, sheet metal / Angleiron

/ C-cleats as required, G.I.fasteners, bolts, nuts and washers, guide vanes as required, supports shall be galvanised threaded rods etc complete.

Makes : Tata / Zindal

 

 

 

1232

a

20 Guage

1

Sqft

110

1233

b

22 Guage

1

Sqft

100

1234

c

24 Guage

1

Sqft

80

 

 

THERMAL INSULATION

 

 

 

 

ELEC-6.6.6

Supply and fixing of …...mm thickness closed cell nitrile

rubber(ClassO)insulationonexistingductafterapplying2 coats of cold setting adhesive (CPRX Compound). The joints shall be sealed with 50mm wide and 3mm thick self adhesive nitrile rubber tape insulation complete as per specifications.

 

 

 

1233

a

6 mm

1

Sqmt

400

1234

b

9 mm

1

Sqmt

565

1235

c

12 mm

1

Sqmt

750

1236

d

19 mm

1

Sqmt

900

1237

e

25 mm

1

Sqmt

1300

 

ELEC-6.6.7

Supply and fixing of …...mm thickness closed cell nitrile rubber(ClassO)insulationonexistingductafterapplying2 coats of cold setting adhesive (CPRX Compound). The joints shall be sealed with 50mm wide and 3mm thick self adhesive nitrile rubber tape insulation complete with star bond coating and covered with 24 guage alluminium claddingasperspecificationsforoutdoorapplications.

 

 

 

1235

a

6 mm

1

Sqmt

450

1236

b

9 mm

1

Sqmt

610

1237

c

12 mm

1

Sqmt

820

1238

d

19 mm

1

Sqmt

1000

1239

e

25 mm

1

Sqmt

1400

1240

ELEC-6.6.8

Supply and fixing of 40mm thick thermocole insulation of 16kgdensitywithGImeshand12mmthickcementmortor

plastering for out door unit.

 

1

 

Sqft

 

68

1241

ELEC-6.6.9

Supplyandfixingof40mmthickglasswoolof24kgdensity with alluminium foil insulation for indoorduct.

 

1

 

Sqft

 

55

1242

ELEC-6.6.10

Supply, installation, testing and commissioning of GI

volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, flnges etc as per specifications. The thickness of the damper frame shall be 16 guage and damper plate shall be 18 guage.

 

 

1

 

 

Sqmtr

 

 

8600

1243

ELEC-6.6.11

Supplyandfixingofalluminiumpowdercoatedsupplyair

grill with volume control dampers.

1

Sqft

615

1244

ELEC-6.6.12

Supplyandfixingofalluminiumpowdercoatedsupplyair

diffuser with volume control dampers.

1

Sqft

700

1245

ELEC-6.6.13

Supplyandfixingofalluminiumpowdercoatedsupplyair

diffuser without volume control dampers.

1

Sqft

600

1246

ELEC-6.6.14

Supply and fixing of angular iron frame with 2 coats of

zincromat red oxide for installation of air cooling unit.

1

No

4360

1247

ELEC-6.6.15

Installationandcommissioningchargesforaircoolingunit.

 

1

 

No

 

3630

1248

ELEC-6.6.16

Supply,installation,testingandcommissioningofthedrain line with CPVC pipes with all accessories and insulation with6mmthickclosedcellnitrilerubberofthefollowing

sizes.

 

 

 

 

a

25 mm

1

RM

190

 

b

32 mm

1

RM

240

 

6.7

STABILIZERS

 

 

 

 

ELEC-6.7.1

Supplyof----------------- Stabilizer

Makes : V-Guard / Real Guard / Uni Stab / ITL.

 

 

 

1249

a

Supply of 0.5 KVA Stabilizer

1

No

920

1250

b

Supply of 1.0 KVA Stabilizer.

1

No

1500

1251

c

Supply of 3.0 KVA Stabilizer

1

No

1900

1252

d

Supply of 4.0 KVA Stabilizer

1

No

2500

1253

e

Supply of 5.0 KVA Stabilizer

1

No

3000

 

ELEC-6.7.2

Supplyof----------------- Stabilizer

Makes :Keeline / Soft Line / Capri.

 

 

 

1254

a

Supply of 0.5 KVA Stabilizer

1

No

720

1255

b

Supply of 1.0 KVA Stabilizer.

1

 

1290

1256

c

Supply of 3.0 KVA Stabilizer

1

No

1660

1257

d

Supply of 4.0 KVA Stabilizer

1

No

2280

1258

e

Supply of 5.0 KVA Stabilizer

1

No

2740

 

 

SECTION - 7

 

 

 

 

7.1

SWAGED POLES / OCTOGONAL POLES, GARDEN POSTS AND ACCESSORIES

 

 

 

 

 

SWAGED POLES

 

 

 

1259

ELEC-7.1.1

Fabrication, supply and transportation of all sizes swaged

poles up to site confirming to IS 2713 / 1980 specifications. The pole should be painted with primary coat of red oxide and black bituminous paint up to ground level with base plate,includingcostofallmaterialsetc.,complete.(Rateper

K. G)

 

 

1

 

 

Kg

 

 

67

 

 

M S POLES FOR GARDEN POSTS

 

 

 

1260

ELEC-7.1.2

Fabrication and Supply of M.S. Poles for garden posts with

'B' class 60.25mm outer dia with base plate and suitable pole cap including cost and conveyance of all material including fixing of luminaire and labour charges etc., complete. (Rate per K. G)

 

 

1

 

 

Kg

 

 

61

1261

ELEC-7.1.3

Supply of different sizes of M. S. Pipe brackets (Rate per

K.G)

1

Kg

61

 

7.2

OCTOGONAL POLES

 

 

 

 

ELEC-7.2.1

Fabrication,    Transportation    and    supply   of    hot-dip

galvanized Octogonal Pole with BSEN - 10025 grade S 355 JO steel plate for shaft, IS 2062 for base plate with door opening arrangement, including chain for anti theft mechanism, supply of suitable boards with bakelite sheet, din channel for MCB's as per IS specification suitable to withstand     the     wind     speed     of     180     KMPH  for

......................................

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

1262

a

7.50 Mtrs height Pole having dimensions Bottom 130mm, Top 70mm with 3mm thick, base plate 220 x 220 x 12mm and 4 Nos of M20 x 700mm long 'J' bolts along with

template.

 

1

 

No

 

12000

1263

b

9 Mtrs height Pole having dimensions Bottom 155mm,Top 70mm with 3mm thick, base plate 260 x 260 x 16mm and 4 NosofM24x750mmlong'J'boltsalongwithtemplate.

 

1

 

No

 

16900

1264

c

10MtrsheightPolehavingdimensionsBottom175mm,Top 70mm with 3mm thick, base plate 275 x 275 x16mm and 4 NosofM24x750mmlong'J'boltsalongwithtemplate.

 

1

 

No

 

19200

1265

d

12 Mtrs height Pole having dimensions Bottom 200mm, Top90mmwith4mmthick,baseplate320x320x20mmand 4NosofM24x850mmlong'J'boltsalongwithtemplate.

 

1

 

No

 

27000

 

ELEC-7.2.2

Fabrication,    Transportation    and    supply   of    hot-dip

galvanized Octogonal Pole with BSEN - 10025 grade S 355 JO steel plate for shaft, IS 2062 for base plate with door opening arrangement, including chain for anti theft mechanism, supply of suitable boards with bakelite sheet, din channel for MCB's as per IS specification suitable to withstand     the     wind     speed     of     180     KMPH  for

......................................

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

1266

a

7.50 Mtrs height Pole having dimensions Bottom 130mm, Top 70mm with 3mm thick, base plate 220 x 220 x 12mm and 4 Nos of M20 x 700mm long 'J' bolts along with

template.

 

1

 

No

 

10800

1267

b

9 Mtrs height Pole having dimensions Bottom 155mm,Top 70mm with 3mm thick, base plate 260 x 260 x 16mm and 4 NosofM24x750mmlong'J'boltsalongwithtemplate.

 

1

 

No

 

15200

1268

c

10MtrsheightPolehavingdimensionsBottom175mm,Top 70mm with 3mm thick, base plate 275 x 275 x16mm and 4 NosofM24x750mmlong'J'boltsalongwithtemplate.

 

1

 

No

 

17100

1269

d

12 Mtrs height Pole having dimensions Bottom 200mm, Top90mmwith4mmthick,baseplate320x320x20mmand 4NosofM24x850mmlong'J'boltsalongwithtemplate.

 

1

 

No

 

25400

 

7.3

BRACKETS

 

 

 

 

ELEC-7.3.1

Fabrication,Transportationandsupplyof----------------------

---------- standard Bracket made with MS galvanized 50mm dia Pipe.

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

1270

a

1.0 Mtr Length Single Arm

1

No

1300

1271

b

1.0 Mtr length Double Arm

1

No

1610

1272

c

1.50 Mtr Length Single Arm

1

No

1720

1273

d

1.50 Mtr length Double Arm

1

No

2900

 

ELEC-7.3.2

Fabrication,Transportationandsupplyof----------------------

---------- standard Bracket made with MS galvanized 50mm dia Pipe.

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

1274

a

1.0 Mtr Length Single Arm

1

No

1250

1275

b

1.0 Mtr length Double Arm

1

No

1540

1276

c

1.50 Mtr Length Single Arm

1

No

1640

1277

d

1.50 Mtr length Double Arm

1

No

2760

 

ELEC-7.3.3

Fabrication, Transportation and supply of -------------

complete with all accessories with MS galvanized 50mm dia Pipe.

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

1278

a

1.0 Mtr sword type or any decorative Single arm bracket

with dooms

1

No

3650

1279

b

1.0 Mtr sword type or any decorative double arm bracket

with dooms.

1

No

4300

1280

c

1.5 Mtr sword type or any decorative Single arm bracket

with dooms

1

No

4100

1281

d

1.5 Mtr sword type or any decorative double arm bracket

with dooms.

1

No

5350

 

ELEC-7.3.4

Fabrication, Transportation and supply of of -------------

complete with all accessories with MS galvanized 50mm dia Pipe.

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

1282

a

1.0 Mtr sword type or any decorative Single arm bracket

with dooms

1

No

3480

1283

b

1.0 Mtr sword type or any decorative double arm bracket

with dooms.

1

No

4100

1284

c

1.5 Mtr sword type or any decorative Single arm bracket

with dooms

1

No

3900

1285

d

1.5 Mtr sword type or any decorative double arm bracket

with dooms.

1

No

5060

 

ELEC-7.3.5

Fabrication,Transportationandsupplyof-----------------------

-bracket with PU paint complete with all accessories with MS galvanized 50mm dia Pipe.

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

1286

a

1.5 Mtr decorative galvanized Single arm

1

No

4830

1287

b

1.5 Mtr decorative galvanized double arm

1

No

9120

 

ELEC-7.3.6

Fabrication,Transportationandsupplyof-----------------------

-bracket with PU paint complete with all accessories with MS galvanized 50mm dia Pipe.

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

1288

a

1.5 Mtr decorative galvanized Single arm

1

No

4600

1289

b

1.5 Mtr decorative galvanized double arm

1

No

8690

 

7.4

HIGH MAST POLES

 

 

 

1290

ELEC-7.4.1

Fabrication, transportation and supply of 12 Mtrs Polygon High Mast with single section of 3mm thick of Bottom 360mmandTop150mmdiawithBSEN-10025gradeS355 JO steel plate for shaft, IS 2062 for base plate,having a base plate of size 520mm dia 16mm thick with its accessories. Mastshallbeinsinglesectionfor12Mtrsand2sectionsfor

16 and 20 Mtrs. Mast shall be hot dip galvanized and suiatbleforwindvelocityof180KMPH asperIS875part3 includingheadframe,2pointsuspensionsystemwithsteel rope 6mm dia (7/19) construction double drum winch / power tool operating speed of 900 RPM, and necessary cable trailer connections and single speed motor with M24 x800mmfoundationboltsofrequiredquantity,suitablefor 6 luminaires with GLS type aviation twinlamp.

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

106000

1291

ELEC-7.4.2

Fabrication, transportation and supply of 12 Mtrs Polygon High Mast with single section of 3mm thick of Bottom 360mmandTop150mmdiawithBSEN-10025gradeS355 JO steel plate for shaft, IS 2062 for base plate,having a base plate of size 520mm dia 16mm thick with its accessories. Mastshallbeinsinglesectionfor12Mtrsand2sectionsfor

16 and 20 Mtrs. Mast shall be hot dip galvanized and suiatbleforwindvelocityof180KMPH asperIS875part3 includingheadframe,2pointsuspensionsystemwithsteel rope 6mm dia (7/19) construction double drum winch / power tool operating speed of 900 RPM, and necessary cable trailer connections and single speed motor with M24 x800mmfoundationboltsofrequiredquantity,suitablefor 6 luminaires with GLS type aviation twinlamp.

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

100000

1292

ELEC-7.4.3

Fabrication, transportation and supply of 16 Mtrs Polygon HighMastwithtwosectionsofBottom4mmthickandTop section with 3mm thick with GLS type aviation lamp of Bottom 360mm and Top 150mm dia with BSEN - 10025 grade S 355 JO steel plate for shaft, IS 2062 for base plate, having a base plate of size 560mm dia 25mm thick with its accessories. Mast shall be in 2 sections and should be hot dipgalvanizedandsuiatbleforwindvelocityof180KMPH as per IS 875 part 3 including head frame, 2 point suspension system with steel rope 6mm dia (7/19) construction double drum winch / power tool operating speed of 900 RPM, and necessary cable trailer connections and single speed motor with M 24 x 800 mm foundation bolts of required quantity with GLS type aviation twin lamp

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

138000

1293

ELEC-7.4.4

Fabrication, transportation and supply of 16 Mtrs Polygon HighMastwithtwosectionsofBottom4mmthickandTop section with 3mm thick with GLS type aviation lamp of Bottom 360mm and Top 150mm dia with BSEN - 10025 grade S 355 JO steel plate for shaft, IS 2062 for base plate, having a base plate of size 560mm dia 25mm thick with its accessories. Mast shall be in 2 sections and should be hot dipgalvanizedandsuiatbleforwindvelocityof180KMPH as per IS 875 part 3 including head frame, 2 point suspension system with steel rope 6mm dia (7/19) construction double drum winch / power tool operating speed of 900 RPM, and necessary cable trailer connections and single speed motor with M 24 x 800 mm foundation bolts of required quantity with GLS type aviation twin lamp

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

132000

1294

ELEC-7.4.5

Fabrication, transportation and supply of 20 Mtrs Polygon HighMastwithtwosectionsofBottom4mmthickandTop section with 3mm thick of Bottom 410mm and Top 150mm dia with BSEN - 10025 grade S 355 JO steel plate for shaft, IS 2062 for base plate, having a base plate of size 570mm dia 25mm thick with its accessories. Mast shall be in 2 sections and should be hot dip galvanized and suiatble for wind velocity of 180 KMPH as per IS 875 part 3 including headframe,2pointsuspensionsystemwithsteelrope6mm dia (7/19) construction double drum winch / power tool operating speed of 900 RPM, and necessary cable trailer connections and single speed motor with M 24 x 800 mm foundation bolts of required quantity with GLS type aviation twinlamp.

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

172000

1295

ELEC-7.4.6

Fabrication, transportation and supply of 20 Mtrs Polygon HighMastwithtwosectionsofBottom4mmthickandTop section with 3mm thick of Bottom 410mm and Top 150mm dia with BSEN - 10025 grade S 355 JO steel plate for shaft, IS 2062 for base plate, having a base plate of size 570mm dia 25mm thick with its accessories. Mast shall be in 2 sections and should be hot dip galvanized and suiatble for wind velocity of 180 KMPH as per IS 875 part 3 including headframe,2pointsuspensionsystemwithsteelrope6mm dia (7/19) construction double drum winch / power tool operating speed of 900 RPM, and necessary cable trailer connections and single speed motor with M 24 x 800 mm foundation bolts of required quantity with GLS type aviation twinlamp.

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

165000

 

7.5

FEEDER PILLER BOX

 

 

 

 

ELEC-7.5.1

Supply and fixing of suitable out door feeder piller box of size made with 14 SWG CRCA sheet with double door arrangement, making powder coating after processing of 7 Tank process, lock and key, hinges, rubber gasket, danger board,suitable angle iron stand for mounting the feeder pillar with cement concrete, including Supply and fixingof Legrand/Schniedermake-------------------------------------------

---- as out goings, indication lamps, din channel, 6 Sqmm 3 corecoppercableforinviduallightcontrol,connectors,bus bars, shroudings, gland plates and provision for 3 phase energy meter etc., complete for finished item of work and suitable wiring provision for connecting the nature switch withfollowing.

 

 

 

1296

a

40A 4 Pole Isolatorasincomer,          6 Nos 6-32A SPMCBs

 

1

 

No

 

18500

1297

b

63A, 4 Pole isolatorasincomer,         6 Nos 6-32A SPMCBs

 

1

 

No

 

18600

1298

c

63A, 4 Pole isolatorasincomer,         9 Nos 6-32A SPMCBs

 

1

 

No

 

19300

 

ELEC-7.5.2

Supply and fixing of suitable out door feeder piller box of size made with 14 SWG CRCA sheet with double door arrangement, making powder coating after processing of 7 Tank process, lock and key, hinges, rubber gasket, danger board,suitable angle iron stand for mounting the feeder pillar with cement concrete, including Supply and fixingof Legrand/Schniedermake-------------------------------------------

asoutgoings,indicationlamps,dinchannel,6Sqmm3core copper cable for invidual light control, connectors, bus bars, shroudings, gland plates and provision for 3 phase energy meter etc., complete for finished item of work and suitable wiring provision for connecting the nature switch withfollowing.

 

 

 

1299

a

40A-63A, 4 Pole MCBasincomer,        6 Nos 6-32A SPMCBs

 

1

 

No

 

19700

1300

b

63A, 4 Pole MCBasincomer,               9 Nos 6-32A SPMCBs

 

1

 

No

 

20300

 

7.6

ERRECTION OF HIGH MAST POLES

 

 

 

1301

ELEC-7.6.1

Earth work exacavation with a approximate quantity of4.0 Cum for errection of 12 Mtrs high mast and refilling with a quantity of 0.53 Cum of PCC 1:4:8, 1.50 Cum M 20 grade concrete and (80 Kgs) reinforced steel of 12mm / 10mm / 8mm,Soilbearingcapacityof10T/Sqm,Anchorplatewith costandconveyanceofallabovematerialsincludinglabour charges for errection of High Mast and Carraige etc complete including soiltesting.

 

 

 

 

1

 

 

 

 

No

 

 

 

 

28100

1302

ELEC-7.6.2

Earth work exacavation with a approximate quantity of6.0 Cum for errection of 16 Mtrs high mast and refilling with a quantity of 0.65 Cum of PCC 1:4:8, 2.60 Cum M 20 grade concrete and (110 Kgs) reinforced steel of 12mm / 10mm / 8mm,Soilbearingcapacityof10T/Sqm,Anchorplatewith costandconveyanceofallabovematerialsincludinglabour charges for errection of High Mast and Carraige etc complete including soiltesting.

 

 

 

 

1

 

 

 

 

No

 

 

 

 

35800

1303

ELEC-7.6.3

Earth work exacavation with a approximate quantity of7.0 Cum for errection of 20 Mtrs high mast and refilling with a quantity of 0.75 Cum of PCC 1:4:8, 3.60 Cum M 20 grade concrete and (140 Kgs) reinforced steel of 12mm / 10mm / 8mm,Soilbearingcapacityof10T/Sqm,Anchorplatewith costandconveyanceofallabovematerialsincludinglabour charges for errection of High Mast and Carraige etc complete including soiltesting.

 

 

 

 

1

 

 

 

 

No

 

 

 

 

45600

 

7.7

CONICAL POLES

 

 

 

1304

ELEC-7.7.1

Fabrication,transportation and supply of MS hot dip galvanized 9.0 Mtrs long Conical poles with 3mm thickHT steel plate with a bottom 173mm dia and top 75mm dia, base plate of size 275mmx275mmx16mm thick welded to bottom of pole, terminal box with door size of 500mm x 100mm with all accessories connector and fuse base and a fixing arrangements for advertisements holdings, foundation bolts with washers and nuts 4 sets. including S&F of 1.0 mtrs C type decorative single arm with painted bracket with dooms either sides complete with all accessories as per the requirements at site and as per the directions of field engineers during execution for finished item ofwork.

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

 

 

 

1

 

 

 

 

 

 

No

 

 

 

 

 

 

15700

1305

ELEC-7.7.2

Fabrication,transportation and supply of MS hot dip galvanized 9.0 Mtrs long Conical poles with 3mm thickHT steel plate with a bottom 173mm dia and top 75mm dia, base plate of size 275mmx275mmx16mm thick welded to bottom of pole, terminal box with door size of 500mm x 100mm with all accessories connector and fuse base and a fixing arrangements for advertisements holdings, foundation bolts with washers and nuts 4 sets. including S&F of 1.0 mtrs C type decorative single arm with painted bracket with dooms either sides complete with all accessories as per the requirements at site and as per the directions of field engineers during execution for finished item ofwork.

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

 

 

 

1

 

 

 

 

 

 

No

 

 

 

 

 

 

14300

1306

ELEC-7.7.3

Fabrication,transportation and supply of MS hot dip galvanized 10.0 Mtrs long Conical poles with 3mm thick HTsteelplatewithabottom184mmdiaandtop75mmdia, base plate of size 275mmx275mmx16mm thick welded to bottom of pole, terminal box with door size of 500mm x 100mm with all accessories connector and fuse base and a fixing arrangements for advertisements holdings, foundation bolts with washers and nuts 4 sets. including S&Fof1.5mtrsCtypedecorativeDoublearmwithpainted bracket with dooms either sides complete with all accessories as per the requirements at site and as per the directions of field engineers during execution for finished item ofwork.

Makes: BAJAJ / VALMONT / TRANSRAIL

 

 

 

 

 

 

1

 

 

 

 

 

 

No

 

 

 

 

 

 

18000

1307

ELEC-7.7.4

Fabrication,transportation and supply of MS hot dip galvanized 10.0 Mtrs long Conical poles with 3mm thick HTsteelplatewithabottom184mmdiaandtop75mmdia, base plate of size 275mmx275mmx16mm thick welded to bottom of pole, terminal box with door size of 500mm x 100mm with all accessories connector and fuse base and a fixing arrangements for advertisements holdings, foundation bolts with washers and nuts 4 sets. including S&Fof1.5mtrsCtypedecorativeDoublearmwithpainted bracket with dooms either sides complete with all accessories as per the requirements at site and as per the directions of field engineers during execution for finished item ofwork.

Makes: SKIPPER / UTKARSH / LAASMA

 

 

 

 

 

 

1

 

 

 

 

 

 

No

 

 

 

 

 

 

16400

 

7.8

DECORATIVEDRAGONTYPEBRACKETWITHPOLE

 

 

 

 

ELEC-7.8.1

Fabrication, Transportation and supply of hot-dip galvanized Octogonal Pole with BSEN - 10025 grade S 355 JO steel plate for shaft, IS 2062 for base plate with door opening arrangement, including the supply of suitable boardswithbakelitesheetandMCB'sasperISspecification suitable to withstand the wind speed of 180 KMPH for 9 MtrsMountingheightPolehavingdimensionsBottom185 mm,. Top 70mm with 3mm thick, base plate 275 x 275 x 20mm and 4 Nos of M24 x 1000 long 'J' bolts along with templates Including Supply of 1.5M Dragon type decorative------------------------

Makes: VALMONT / BAJAJ / TRANSRAIL

 

 

 

1308

a

galvanised Double Arm with PU Painted bracket.

1

No

26600

1309

b

galvanised Single Arm with PU Painted bracket.

1

No

22800

1310

c

Double arm Galvanised finish bracket.

1

No

22800

1311

d

Single arm Galvanised finish bracket.

1

No

20400

 

ELEC-7.8.2

Fabrication,Transportationandsupplyofhot-dip------------

--CurvedOctogonalPolewithBSEN-10025gradeS355JO steel plate for shaft Including Supply of 0.2M long Single arm bracket, IS 2062 for base plate with door opening arrangement, including the supply of suitable boards with bakelite sheet and MCB's as per IS specification suitable to withstand the wind speed of 180 KMPH for 9 Mtrs Mounting height Curved Pole having dimensions Bottom 180mm,. Top 85mm with 3mm thick, base plate 400 x 400 x 20mm and 4 Nos of M24 x 750 long 'J' bolts along with templates.

Makes: VALMONT / BAJAJ / TRANSRAIL

 

 

 

1312

a

galvanized

1

No

22300

1313

b

galvanized PU Paint finish

1

No

30200

 

7.9

THERMO PLASTIC POLE BOXES

 

 

 

 

ELEC-7.9.1

Supply of following sizes thermo plastic pole boxes IP 65 protection.

Make : Hensel / Sintex / Sadhrish

 

 

 

1314

a

200X150X100

 

 

720

1315

b

250X200X120

 

 

890

1316

c

300X150X170

 

 

1040

1317

d

300X200X125

 

 

1120

1318

e

300X300X170

 

 

1480

1319

f

400X300X200

 

 

1600

1320

g

300X450X170

 

 

2020

1321

h

490X390X250

 

 

2230

1322

i

300X600X170

 

 

2400

 

7.10

FOUNDATION AND ERRECTION CHARGES OF

POLES

 

 

 

1323

ELEC-7.10.1

Erection charges for 7.50 Mts long Octagonal pole on

bridge kerb portion (R.C.C). with 4 Nos 8" Anchor bolts/ M20xsuitable "J" type bolts etc duly drilling holes to RCC slab and with V.C.C. M.15 concrete for base concreting up to a height of 8" with necessary Reinforcement work etc. including cost and con veyance of all material and all labour charges etc. complete as directed by thedepartment officers.

 

 

 

1

 

 

 

No

 

 

 

3360

1324

ELEC-7.10.2

Foundation and erection charges with special T&P, for7.50 Mtrs long Octagonal / Conical pole duly erecting on base platedulyproviding4Nosfoundationboltswithnutswith providing of 0.45Mtrx0.45Mtrsx1.20 Mtr size M20 cc work vibrated concreting mixing with necessary steel (10kgs) reinforcement as directed by the field engineers during executionincludingcentering,decentering,watercuringas required, soil exacavation, back filling, muffing removal and coil earthing including all labour charges and cost and conveyance of materials etc.complete.

 

 

 

 

 

1

 

 

 

 

 

No

 

 

 

 

 

4730

1325

ELEC-7.10.3

Foundation and erection charges with special T&P, for 9.00Mtrs / 10Mtrs long Octagonal / Conical pole duly erecting on base plate duly providing 4 Nos foundation bolts with nuts with providing of 0.60Mtrx0.60Mtrsx1.40 Mtr size M20 cc work vibrated concreting mixing with necessary steel (15kgs) reinforcement as directed by the field engineers during execution including centering, decentering, water curing as required, soil exacavation, backfilling,muffingremovalandcoilearthingincludingall labour charges and cost and conveyance of materials etc. complete.

 

 

 

 

 

1

 

 

 

 

 

No

 

 

 

 

 

6300

1326

ELEC-7.10.4

Foundation and erection charges with special T&P, for 12MtrslongOctagonal/Conicalpoledulyerectingonbase platedulyproviding4Nosfoundationboltswithnutswith providing of 0.67Mtrx0.67Mtrsx1.50 Mtr size M20 cc work vibrated concreting mixing with necessary steel (20kgs) reinforcement as directed by the field engineers during executionincludingcentering,decentering,watercuringas required, soil exacavation, back filling, muffing removal and coil earthing including all labour charges and cost and conveyance of materials etc.complete.

 

 

 

 

 

1

 

 

 

 

 

No

 

 

 

 

 

7900

 

7.11

G R P POLES

 

 

 

 

ELEC-7.11.1

Supply and transportation of following glass reinforced polymer (GRP) composite type Conical pole with single arm bracket of length 1Mtr and internal junction box including labour charges etc., complete. Makes: Bajaj / Valmont / Kemrock / Sumip.

 

 

 

1327

a

3.00 Mtrs height, Bottom dia 143mm, Top 76mm, AV thickness 6mm and to withstand maximum wind velocity

155Km/Hr

 

1

 

No

 

9200

1328

b

4.00 Mtrs height, Bottom dia 143mm, Top 76mm, AV thickness 6mm and to withstand maximum wind velocity

155Km/Hr

 

1

 

No

 

11500

1329

c

6.00 Mtrs height, Bottom dia 143mm, Top 76mm, AV thickness 6mm and to withstand maximum wind velocity

155Km/Hr

 

1

 

No

 

14600

1330

d

8.00 Mtrs height, Bottom dia 193mm, Top 76mm, AV thickness 6mm and to withstand maximum wind velocity

155Km/Hr

 

1

 

No

 

19300

1331

e

10.00 Mtrs height, Bottom dia 227mm, Top 76mm, AV thickness 6mm and to withstand maximum wind velocity

155Km/Hr

 

1

 

No

 

27900

 

ELEC-7.11.2

Supplyandtransportationofbasebracketsuitableforglass reinforced polymer (GRP) composite type pole including labour charges etc.,complete.

Makes : Bajaj / Kemrock / Sumip.

 

 

 

1332

a

For 3.00 Mtrs Pole

1

No

1540

1333

b

For 4.00 Mtrs Pole

1

No

1540

1334

c

For 6.00 Mtrs Pole

1

No

1850

1335

d

For 8.00 Mtrs Pole

1

No

2160

1336

e

For 10.00 Mtrs Pole

1

No

5140

 

7.12

CONTROL PANEL BOARD

 

 

 

 

ELEC-7.12.1

Fabrication and erection of ----------------------- sheet steel enclosure for power control cubicle panel / boxes etc., including cutting, bending drilling, welding and reveting etc., complete with cleaning with 7 tank process and painting with powder coating including cost and conveyance of all materials and labour charges.

 

 

 

1337

a

14SWG CRCA

1

Sq Mtr

4380

1338

b

16 SWG CRCA

1

Sq Mtr

4140

1339

c

18SWG CRCA

1

Sq Mtr

3660

 

7.13

METERING EQUIPMENT

 

 

 

 

ELEC-7.13.1

Supply and erection of 0-415V ----------------- on exisiting panel board including connections etc., complete.

MAKES : CONZERVE / ELMEASURE / L&T / SEIMENS.

 

 

 

1340

a

Volt Digital meter

1

No

2000

1341

b

Volt Analog meter

1

No

400

 

ELEC-7.13.2

Supplyanderectionof0-100/200/400/600/1000--------

---------------of size 96x96mm on existing panel board including connections etc., complete.

MAKES : CONZERVE / ELMEASURE / L&T / SEIMENS.

 

 

 

1342

a

Digital Ammeter

1

No

2000

1343

b

Analog Ammeter

1

No

400

1344

ELEC-7.13.3

 

Supply and erection of Digital frequency meter on existing panel board including connections etc., complete.

MAKES : CONZERVE / ELMEASURE / L&T / SEIMENS

 

 

1

 

 

No

 

 

2500

1345

ELEC-7.13.4

Supply and erection of Digital power factor meter, 3phase,

4 wire balanced or unabalanced load 5A, 415V of size 96x96mm on existing box / panel board including connections etc., complete.

MAKES : CONZERVE / ELMEASURE / L&T / SEIMENS.

 

 

1

 

 

No

 

 

2500

 

ELEC-7.13.5

 

SupplyanderectionofL.T.3phaseDigitalmultifunction----

------ for measuring all the parameters (Voltage, Current, Frequency, Power factor, KW, KVA, KWH, KVA, KVAH, KVAR and THD Events) on existing box panel board including connections etc., complete.

MAKES : CONZERVE / ELMEASURE / L&T / SEIMENS.

 

 

 

1346

a

energy meter Class I with LED display

1

No

6500

1347

b

energy meter Class I RS 485 with LED display

1

No

7500

1348

c

energy meter Class 0.5 RS 485 with LED display

1

No

8800

1349

d

energy meter Class I with LCD display

1

No

7500

1350

e

energy meter Class I RS 485 with LCD display

1

No

8400

1351

f

energy meter Class 0.5 RS 485 with LCD display

1

No

9800

1352

g

bidirectional import / export energy meter Class I with

LED display

1

No

14350

1353

h

bidirectional import / export energy meter Class I RS 485

with LED display

1

No

15280

1354

i

bidirectional import / export energy meter Class I with

LCD display

1

No

15280

1355

j

bidirectional import / export energy meter Class I RS 485

with LCD display

1

No

16200

 

ELEC-7.13.6

Supply and erection of ---------------------------------------

Makes : L&T / C&S / SALZAR / HPL MAKE.

 

 

 

1356

a

Selector switch for Voltmeter / Ammeter on the existing

panel including connections etc., complete.

1

No

175

1357

b

LED indication lamps on the existing panel board.

1

No

135

1358

c

Push buttons on the existing panel board.

1

No

75

1359

ELEC-7.13.7

Supply and erection of LT current transformer with bar primary 100/5A to 1000 / 5A ratio in the existing panel including connections etc., complete.

MAKE : KAPPA

 

1

 

No

 

440

 

ELEC-7.13.8

Supply and fixing of---------------------- Electronic energy

Meter, 240V AC, 50 HZ as per IS13010 up to 40A range with 200% over load capacity complete with connections etc., complete on the existing board.

Makes : CONZERVE / ELMEASURE / MECO / HPL /

HAVELLS.

 

 

 

1360

a

Single phase

1

No

985

1361

b

Three phase

1

No

2840

 

ELEC-7.13.9

Supply and fixing of ---------------- APFC Relay with connection etc complete.

Makes : L&T / Siemens / EPCOS / Schneider / Elmeasure

 

 

 

1362

a

8 Stage

1

No

12400

1363

b

12 Stage

1

No

14000

1364

c

14 Stage

1

No

16600

 

ELEC-7.13.10

Supply and fixing of ------------------ Rating capacitor duty contactor

Makes : L&T / Siemens / EPCOS / Meher

 

 

 

1365

a

3 KVAR

1

No

1540

1366

b

5 KVAR

1

No

1610

1367

c

8.5 KVAR

1

No

1860

1368

d

10 KVAR

1

No

2020

1369

e

12.5 KVAR

1

No

2160

1370

f

15.0 KVAR

1

No

3000

1371

g

20 KVAR

1

No

3480

1372

h

25.0 KVAR

1

No

3900

1373

i

50.0 KVAR

1

No

10780

 

ELEC-7.13.11

Supply and fixing of detuned reactor 7% 3 phase 440V range

-------------

Makes : L&T / Siemens / EPCOS / Meher

 

 

 

1374

a

5 KVAR

1

No

7800

1375

b

10 KVAR

1

No

12300

1376

c

12.5 KVAR

1

No

13650

1377

d

15 KVAR

1

No

15300

1378

e

20 KVAR

1

No

17850

1379

f

25 KVAR

1

No

18900

1380

g

50 KVAR

1

No

30000

1381

h

75 KVAR

1

No

44700

1382

i

100 KVAR

1

No

60900

 

ELEC-7.13.12

Supply of MPP type heavy duty capacitor of operating voltage

Makes:L&T/Siemens/Schneider/Epcos.

 

 

 

1383

a

not less than 440V of cylyndrical type of 1 KVAR to 2

KVAR

1

KVAR

340

1384

b

not less than 480V of cylyndrical type more than 2 KVAR

1

KVAR

330

1385

c

not less than 440V of box type of 1 KVAR to 4 KVAR

1

KVAR

440

1386

d

not less than 480V of box type of 5 KVAR to 50 KVAR

1

KVAR

400

 

7.14

SUB STATION EQUIPMENT

 

 

 

1387

ELEC-7.14.1

Carryout routine maintenance, servicing and testing of

630A to 1000A L.T.ACB by cleaning fixed contacts,moving contacts and arcchutes including servicing and putting the ACBinperfectworkingconditionafterdettingallrelayand ON, OFF mechanism etc done with only manufacturing companies

 

 

 

1

 

 

 

No

 

 

 

5500

1388

ELEC-7.14.2

Carryout routine maintenance and servicing of LT.Cubical pannel board having approximately 15 to 22 Nos of switches cleaning with power brower and servicing the contacts, tightning the connection of incoming and outgoing cables, and clicking the operating machanism for smoothfunctioningofswitchesandputtingtheminsmooth workingcondition.

 

 

 

 

1

 

 

 

 

No

 

 

 

 

2625

1389

ELEC-7.14.3

Routine maintenance of transformer in operation covering

insulation resistance oil, break down strength. Reconditioning / replacement of silicazel, cleaning of transformer and topping upto oil level if required (extra cost will be paid for oil).

 

 

1

 

 

No

 

 

4500

1390

ELEC-7.14.4

Testing of Transformer oil for dielectric breakdown strength.

 

1

 

No

 

510

1391

ELEC-7.14.5

Insulating H.T. / LT copper / aluminium coils for Transformers.

 

1

 

No

 

310

 

ELEC-7.14.6

Removing  the existing transformer from the plinth /Pole

and refixing the standby transformer of following capacity including  connections  etc.,complete--------------------------------

---

 

 

 

1392

a

Upto 315 KVA

1

No

2550

1393

b

500 / 1000 KVA

1

No

3570

 

ELEC-7.14.7

Replacing old and unserviceable gasket of top cover plate of transformer having following capacity ------------

 

 

 

1394

a

Upto 315 KVA

1

No

770

1395

b

500 / 1000 KVA

1

No

1080

 

ELEC-7.14.8

Replacing old and unserviceable gasket of bushing for the following Transformer capacity.

 

 

 

1396

a

Upto 315 KVA H.T.

1

No

310

1397

b

Upto 500 / 1000 KVA H.T.

1

No

570

1398

c

Upto 315 KVA L.T.

1

No

720

1399

d

Upto 500 / 1000 KVA L.T.

1

No

1480

 

ELEC-7.14.9

Replacement the H.T. / L.T. burntout winding coils of distribution transformer including rewinding, varnishing and vaccuming etc.,duly retaining the removed burnt winding coils by the Contractor / Firm ----------

 

 

 

1400

a

For copper coils

1

Kg

610

1401

b

For aluminium coils

1

Kg

400

 

ELEC-7.14.10

Painting with 2 coats Zinchromate red oxide duly scraping existingpaintfollowedby2coatsofhammertongreypaint etc.,complete.--------------

 

 

 

1402

a

Upto 500 KVA

1

No

3060

1403

b

630 / 1000 KVA

1

No

4080

 

ELEC-7.14.11

Replacing         ----------------------------       for                        distribution Transformer by newone.

 

 

 

1404

a

H.T bushing

1

No

360

1405

b

H.T bushing metal parts

1

No

390

1406

c

L.Tbushing                           Upto 315KVA

1

No

170

1407

d

L.Tbushingfor                         500 / 1000KVA

1

No

180

1408

e

L.T bushingmetalparts              100KVA

1

No

310

1409

f

L.T bushingmetalparts              250 / 315KVA

1

No

510

1410

g

L.T bushingmetalparts              500KVA

1

No

1330

1411

h

L.T bushingmetalparts              1000KVA

1

No

2040

 

ELEC-7.14.12

Dryingtherepairedtransformerwithappropriateheat/air

-----

 

 

 

1412

a

Upto 315 KVA

1

No

3060

1413

b

500 / 1000KVA

1

No

4290

 

ELEC-7.14.13

Loading and Unloadng of transformer from site to Workshop or vice verse-----------------

 

 

 

1414

a

Upto 500 KVA

1

No

4590

1415

b

630 / 1000 KVA

1

No

6940

 

ELEC-7.14.14

FilterationoftransformeroilasperISSspecificationsfilters to die electric strength above 40KV--------------

 

 

 

1416

a

At site

1

Ltr

10

1417

b

At workshop

1

Ltr

7

1418

ELEC-7.14.15

Transformer oil tested as per IS-335 - 1972 (per Ltr)

1

Ltr

122

 

ELEC-7.14.16

Servicing of DBs duly opening the top cover checking the circuits, tigheting the screws, applying tape wherever required and making propoer dressing etc complete.

 

 

 

1419

a

4 Way SPN DB

1

No

40

1420

b

8 Way SPN DB

1

No

80

1421

c

12 Way SPN DB

1

No

120

1422

d

4 Way TPN DB

1

No

120

1423

e

8 Way TPN DB

1

No

240

1424

f

12 Way TPN DB

1

No

360

1425

g

4 Way VTPN DB with MCCBs / MCB Circuits

1

No

200

1426

h

8 Way VTPN DB with MCCBs / MCB Circuits

1

No

300

1427

i

12 Way VTPN DB with MCCBs / MCB Circuits

1

No

400

1428

ELEC-7.14.17

Carryout routine maintenance, servicing and testing of 630A to 3000A HT VCB by cleaning fixed contacts, moving contacts and arcchutes including servicing and putting the VCBinperfectworkingconditionafterdettingallrelayand ON, OFF mechanism etc done with only manufacturing companies/Authoriseddealersofrespectiveswitchgears

 

 

 

1

 

 

 

No

 

 

 

9000

 

7.15

TRANSFORMERS

 

 

 

 

ELEC-7.15.1

Supply and Transportation of KVA TRANSFORMER :

The Transformer shall be designed and manufactured as per IS:1180 OCTC with level-II with initial filling of oil as per IS 335-1993. The basic details of the Transformer are as under.

Makes:Kirloskar/PETE/Esennar/Voltamp/Crompton

/ ABB / Schneider.

 

 

 

 

 

  1. Quantity :1
  2. RatedKVA:........... KVA
  3. Service&Location:ContinuousOutdoorDistribution Transformer
  4. Mounting :Plinth.
  5. Wound : Copper Doublewound
  6. Type:       Core type oilimmersed
  7. Cooling :ONAN
  8. Temp Rise : 40?C inoil

45?C byresistance

  1. VectorGroup:            Dyn11
  2. Primary Connection :Delta
  3. NominalVoltage/Current:                
  4. Highest system Voltage:12000V
  5. PrimaryFrequency          :50 HZ +/-3%
  6. Number ofPhases:         3
  7. Primarywires:          3
  8. Secondary connection :Star
  9. Secondary Volts / Current :433V
  10. Secondaryphases:        3
  11. Secondarywires:          4
  12. Tapsonprimarywindingforprimaryvoltagevariation

: +5% to - 10% in steps of 2.5% of 7 position (6 Steps)

 

 

 

 

 

 

  1. Terminalarrangement.
    1. HV:HTterminalboxasperthesitecondition.
    2. LV:Cableboxsuitabletoreceive---------------- Sq.mm

XLPE cable

  1. LV:One separate terminal forearthing.
  2. TotalLossesat50%Loading[Watts][Max]--------- as perIS
  3. TotalLossesat100%Loading[Watts][Max]-------- as perIS
  4. PercentageImpedanceat75deg.Cat------------ as perIS
  5. No Load current: Less than 2% of full loadcurrent.

 

 

 

 

 

  1. Standrad Fittings &Accessories.
    1. Rating and terminal marking plate:One
    2. LiftingLugs:Two
    3. Off-circuit tap switch:One
    4. EarthingTerminals           :Two
    5. Radiators(Attachable)                   :Adequate
    6. Explosion vent with Diaphragm:One
    7. Conservator with Drainplug:one
    8. Oil filling hole with cap:One
    9. Oil level indicator :One
    10. Dehydrating Silicagel Breather :One
    11. Terminal Arrangement: HV With TreminalBox
    12. Terminal Arrangement : LV CableBox
    13. Separate Neutral Bushing :One
    14. Filter valve with blanking plate :One
    15. Draincumfiltervalvewithblankingplate:One
    16. Air release device :One
    17. Thermometer Pocket :One
    18. Four :Unidirectional flatrollers
    19. One :10Cm dial thermometer(Rigid stemtype)

 

 

 

1429

a

160 KVA Copper Wound Transformer

1

No

500000

1430

b

200 KVA Copper Wound Transformer

1

No

550000

1431

c

250 KVA Copper Wound Transformer

1

No

600000

1432

d

315 KVA Copper Wound Transformer

1

No

800000

1433

e

400 KVA Copper Wound Transformer

1

No

950000

1434

f

500 KVA Copper Wound Transformer

1

No

1050000

1435

g

630 KVA Copper Wound Transformer

1

No

1130000

1436

h

1000 KVA Copper Wound Transformer

1

No

1480000

 

ELEC-7.15.2

Supply and transportation of 3 Phase, 50 Hz, Dry type,

Indoor type copper wound Transformer designed and manufactured as per IS 2026-1977 and IS 11171-1985, connecteddeltaonprimarysideandStaronsecondaryside with additional neutral brought out  on  load  side,  11000V / (433V / 415V) with HV off load tap changing + 5% to -5% in steps of 2.5%, temporature rise by the resistance   90?C   complete   with   the   following  standardmountings.

Makes:Kirloskar/PETE/Esennar/Voltamp/Crompton

/ ABB / Schneider.

 

 

 

 

 

  1. RatedKVA:........... KVA (CastResin)
  2. Service:                Indoor
  3. Mounting:              Floor.
  4. Copperwound:        Double.
  5. Type ofcooling:        ANAN.
  6. Insulation Class : ClassF
  7. Temparature rise by resistance :90?C
  8. VectorGroup:           Dyn11

 

 

 

 

 

  1. Primary Connection :Delta
  2. PrimaryVolts:         11000
  3. Primry Frequency : 50 12.PrimaryPhases:        3
  1. Primarywires:          3
  2. Secondary connection :Star
  3. SecondaryVolts:          433V /415V
  4. Secondaryphases:        3
  5. Secondarywires:          4
  6. Tapsonprimarywindingforprimaryvoltagevariation

:

+5.0% to - 10.0% in steps of 2.5% through links.

 

 

 

 

 

19. Terminal arrangement.

 

 

 

 

 

a. HV: Cable end box b. LV : Cable end box

 

 

 

 

 

20. No loadlosses(Watts):............. As per ISspecifications

 

 

 

 

 

21. Loadlosses(Watts):............... As per ISspecifications

 

 

 

 

 

22.Impedance(Z%):.................... As per ISspecifications

 

 

 

 

 

23. Fittings & Accessories.

a. Rating and terminal marking plate b. Earthing terminals

  1. LiftingLugs
  2. Winding temporatureIndicator
  3. Seperate neutralbushing
  4. Uni directional flatrollers.

 

 

 

1437

a

250 KVA Copper Wound Cast Resin Transformer

1

No

670000

1438

b

315 KVA Copper Wound Cast Resin Transformer

1

No

770000

1439

c

400 KVA Copper Wound Cast Resin Transformer

1

No

870000

1440

d

500 KVA Copper Wound Cast Resin Transformer

1

No

1050000

1441

e

630 KVA Copper Wound Cast Resin Transformer

1

No

1150000

1442

f

750 KVA Copper Wound Cast Resin Transformer

1

No

1350000

1443

g

1000 KVA Copper Wound Cast Resin Transformer

1

No

1700000

1444

ELEC-7.15.3

Supply , Fabrication, Transportation and fixing of Boxtype RS Joist pole made with 2 Nos 175X85 mm ( ISMB Modified ) or equivalent about 30'-0 length / 9.1 mtrs length poles welded together including excavation of pit, coil earthing, Special T&P, painting of Pole with 1 coat of Red oxide and 2 coats of alluminium paint, CC 1:3:6 upto ground and 1:2:4 for Couping work, 200A AB Switch, HG fuse sets, required angle iron channels, clamps, nuts and bolts, 11KV pin insulators, 2Nos GI pipe earthings as per the IS with brick massonry chamber including labour and transportation charges etc.,complete.

 

 

 

 

 

1

 

 

 

 

 

No

 

 

 

 

 

60000

1445

ELEC-7.15.4

Supply, Fabrication, Transportation and erection of DP structure made with 2 Nos 175mm x 85mm ( ISMB Modified ) or equivalent about 30'-0 length / 9.1 mtrs length RS joist pole erection of the same Including excavation of pit in all kinds of soil including breaking stones, concreting with (1:3:6) mixture base plate, coil earthing back filling, 1:2:4 for couping including red oxide primarypaintingandtwocoatsofaluminiumpaintingetc., completeasrequiredwithfollowingasperCEIGnorms.

 

 

 

 

1

 

 

 

 

No

 

 

 

 

105000

 

 

a). 400A AB Switch-1No

 

 

 

 

 

b) HG Fuse sets-1No

 

 

 

 

 

c). LAS-1set.

 

 

 

 

 

d) Required Number of 11KV pin and disc insulatiors.

 

 

 

 

 

e) Required length of 100X50mm and 75X40 mm ISMC chanell iron including two coats of redoxide and two coats

of enamil paint ect for finished item of work.

 

 

 

 

 

f) 11KV pin insulators and disc insulators.

 

 

 

 

 

g) AB switch operating pipe with handle and lock and key

arrangements.

 

 

 

 

 

h). "0" SWG or 8.25 mm dia hard drawn bare copper wire including copper binding wire etc., complete as required

including connections.

 

 

 

 

 

i) 40X6mm GI strip for the DP structure earthing.

 

 

 

 

 

j) 25X6mm copper strip for lightning arrestors earthing.

 

 

 

 

 

k) 600X600mmX3,15mm thick copperplate earthings as per

NEC with brick massonary chambers - 2 Nos

 

 

 

 

 

l) GI pipe earthing for the Double pole structure with brick

massonry chambers as per IS - 2 Nos

 

 

 

1446

ELEC-7.15.5

Providing independent earthing for Important equipment with 40mm dia 'B' class 2.5m long G.I pipe and 19mm dia 'B' class G.I pipe of 0.3mtr. long connected with reducer providing G.I funnel with mesh enclosed in C.C/ brick massonry chamber of 450m x 450m x 400mm with R.C.C. Slabcoverdulyprovidingstaggeredholesfillingwith20Kg Saltand40KgCharcoalor40Kgbentonitepowderfromthe bottom of the pipe giving earth connection from electrode through G.I strip of 40 x 6mm x 200mm length with all accessories and labour charges complete, as per IS specifications 732/1982 (PartII)

 

 

 

 

 

1

 

 

 

 

 

No

 

 

 

 

 

4200

1447

ELEC-7.15.6

Providing independent earthing by exacavating a pit to a depth of 2.25Mtr in all soils as per size specified in thedata for Sophisticated Electronic equipment with 600mm x 600mm x 3.15mm thick copper plate rigidly fixed to 40mm dia 'B' Class G.I Pipe of 2.5Mtr length as per National Electric Code and earth connection from electrode GI strip of25mmx5mmx200mmlengthtobeboltedwithnutbolts to G.I.pipe including 25mm x 3mm copper strip of 6Mtrs length connected from plate to GI strip including filling with 20Kg Salt and 40Kg Charcoal or 40Kg bentonite powder from the bottom of the pipe and providing CC / Brick massonry chamber 450mmX450mmX400mm and covered with R.C.C. Slab including all accessories and labourchargesetccompleteasperISspecification732/1982 (PartII).

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

12000

1448

ELEC-7.15.7

Providing transformer plinth 1.2 x 1.2 x 1.5 mtr in size with

necessary excavation in ground at the bottom with 150mm thick 1:2:4 cement concrete raft at the bottom and top and 225mm thick wall constructed in stone masonry and remaking hallow portion shall be filled with stone chips duly plastered 20mm thick outsides including watering etc., complete.

 

 

 

1

 

 

 

No

 

 

 

10000

1449

ELEC-7.15.8

Providing CTPT plinth 600mm x 600mm x 2.1 mtr in size

with necessary excavation in ground at the bottom with 150mm thick 1:2:4 cement concrete raft at the bottom and topdulyplastered20mmthickoutsidesincludingwatering etc.,complete.

 

 

1

 

 

No

 

 

6000

1450

ELEC-7.15.9

Providing independent earthing for Important equipment with 100mm dia Heavy gauge C.I ( Cast iron ) pipe with Flange2.5mlongenclosedinC.C/brickmassonrychamber of 450m x 450m x 400mm with R.C.C. Slab cover duly providing staggered holes filling with salt and charcoal from the bottom of the pipe giving earth connection from electrode through G.I strip of 40 x 6mm x 200mm length with all accessories and labour charges complete, as per IS specifications 732/1982 (PartII)

 

 

 

 

1

 

 

 

 

No

 

 

 

 

7500

1451

ELEC-7.15.10

Supply,Transportation,InstallationandCommissioningof 11 KV, 630A, 25 KA Outdoor type Load Break Switch as detailed below with suitable CC foundation and 2 Nos GI pipe earthing with brick massonry chambers etc complete for finished item ofwork.

  1. Load break switch: 11KV,630A, 25 KA with fuse trip, earth switch, manually operated spring chargesdmechanis with 2 no + 2NC.
  2. HT HRC fuse upto 63A - 3nos.
  3. Bus barconnection.
  4. Indicationlamps.
  5. Manual trip Pushbuttion.

Make Megawin/Pentagon/ Venkateshwara/Jyothi.

 

 

 

 

 

 

1

 

 

 

 

 

 

No

 

 

 

 

 

 

115000

1452

ELEC-7.15.11

Supply, Installation, Testing and commissioning of indoor typefloormountedmetalcladVCBpanelwith3NosVCBs, totallyenclosedandfullyinterlockedhorizantaldrawout, horizantal isolated type breaker as per IS 13118 Specifications and as amended upto date and additional specifications, having capacities mentioned below, single break, trip free mechanism, motorised operated spring / manually charged and auto/manually closed breaker suitable for use on 11KV, 3 Phase, 50 HZ AC supply with short circuit fault level of 350 MVA, complete with self contained, fully inter locked rack in and rack out mechanism,airinsulatedbutencapsulatedcopperbusbars of 630A capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring charging motor, 110V DC closing and tripping coil, safety shutter assembly, shunt trip coil and auxilary switch of 4 NO + 4 NC and equipped with the following switchgears and accessories including connections suitable for XLPE 11 KV cable, cable entry from bottom, end termination with heat shrinkable jointing material etc as required including construction of suitable CC works for VCB's etc complete. Makes:Kirloskar / Schneider / Siemens /ABB

 

 

 

 

 

 

 

 

 

 

 

 

 

1050000

 

 

INCOMER-1No

 

 

 

 

 

Vaccum circuit breaker electrical drawout type TP 11 KV 630Anotlessthan18KAratedshortcircuitratingcurrent-

1No

 

 

 

 

 

POTENTIAL TRANSFORMER:1 No. 11000 / 110 Volts PT,

Class 1 accuracy, 100 VA burden with HT/LT fuses.

 

 

 

 

 

CURRENTTRANSFORMER:3NosepoxyresincastCTsof ratio 100-300/5A, 15VA burden and accuracy class 1.0for

metering and class 5P10 for protection

 

 

 

 

 

METERING

 

 

 

 

 

1No -digital type Ammeter and selector switch of makes

CONZERV/EQVT

 

 

 

 

 

1 No digital type Voltmeter with 0-15KV range, slector switch for Voltmeter of makes CONZERV/EQVT

 

 

 

 

 

1No-Digital         Multifunction         meter        of        makes

CONZERV/EQVT

 

 

 

 

 

Heater ON/OFF switch with space heater and thermostat, single phase switch with socket cubical lamp for panel illunmination with door limit switch ,MCB's for AC & DC

control.

 

 

 

 

 

LED indication lamps for breaker on, breaker off, spring

charge indication, trip ciruit healthy with push button, Autotripindicationmeter,Auxilarycontactforservicetest position(4No+4NC)serviceandtestpositionsandR/Y/B indicationlamps.

 

 

 

 

 

PROTECTION: 1 Nos. Microprocessor based IDMTL 3

overcurrentand1earthfaultrelaywithOvercurrent,earth fault and short circuitprotection.

 

 

 

 

 

High speed tripping relay

 

 

 

 

 

ANNUNCIATION: 8 Window annunciation panel with

push buttons and hooters.

 

 

 

 

 

POWER PACK: Supply, Installation, testing and

commissioning of Power pack with 230V input and 110V DC continuous output suitable for closing / tripping / indication of 3 Nos VCBs with 2.5sqmm FRLS coppercable etc asrequired.

 

 

 

 

 

OUTGOINGS - 2Nos

 

 

 

 

 

630A VCBs draw out type TP 11 KV 630 A not less than 16

KA rated short circuit rating current.

 

 

 

 

 

Each breaker shall consist the following.

 

 

 

 

 

CURRENT TRANSFORMER: Epoxy resin cast CTs of ratio 300/5A, 15VA burden and accuracy class 1.0 for metering

and class 5P10 for protection - 3 Nos

 

 

 

 

 

Digital type Ammeter and selector switch - 1 No

Makes : CONZERV / EQVT

 

 

 

 

 

Digital Multifunction meter - 1 No

Makes: CONZERV / EQVT

 

 

 

 

 

PROTECTION : Microprocessor based IDMTL 3 over currentand1earthfaultrelaywithOvercurrent,earthfault

and short circuit protection - 1 No

 

 

 

 

 

High speed tripping relay

 

 

 

 

 

Auxiliary relay for bucholz A/T,OTI A/T, WTI A/T

 

 

 

 

 

Heater ON/OFF switch with space heater and thermostat, single phase switch with socket cubical lamp for panel illunmination with door limit switch ,MCB's for AC & DC

control.

 

 

 

 

 

INDICATION LAMPS: LED indication lamps for breaker on, breaker off, spring charge indication, trip ciruit healthy with push button, Auto trip indication meter, Auxilary contact for service test position ( 4No+ 4 NC) service and test positions and R/Y/B indication lamps.

 

 

 

 

 

ANNUNCIATION: 8 Window annunciation panel with

push buttons and hooters.

 

 

 

 

 

1No.rearentrycableboxsuitabletoreceive11KV,1runof

3CX 120 sqmm cable(XLPE) .

 

 

 

 

 

1 set of misc items like control fuses , control wiring , inter connections, nuts, bolts, bus trunking including all

connected accessories etc.

 

 

 

 

 

1 Set of 11 KV, 630A, 350 MVA alluminium Bus Bar.

 

 

 

 

 

Note : If out going breaker quantity is increased, Rs.3.00 Lakhs per each breaker to be added to the above.

 

 

 

1453

ELEC-7.15.12

Supply,transpotation,installation,testing                                                                                          and commissioning of HT INDOOR type single panel switchgear with VCB of floor mounted, metal clad 11KV, 630A,notlessthan18.4KA(350MVA)VCBPanel,with1No VCBs totally enclosed and horizantal drawout type, horizontal isolation type breaker as per IS 13118 as amended upto date and additional specifications having capacities as mentioned below , single break trip free mechanism, motorised/manually charged and auto manually closing breaker suitable for use on 12KV,3phase,50HZ AC supply with self contained fully interlocked rackin and rackout mechanism air insulated allumium Busbars of 630A capacity, Breaker featured with ON/OFF indicator with hand trip device, spring reliefcoil, shunt trip coil and auxillary switch of 6NO + 6NC and equiped with following switchgears and accessories incommingconnectionssuitablefor3x95SqmmXLPE11KV Cable as required etc complete with adaptor box for outgoingtermination.

Makes: Kirloskar / Schneider / Siemens / Crompton Greaves / ABB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400000

 

 

Incoming-

 

 

 

 

 

11KV, 630A,not less than 18.40KA VCB - 1No.

 

 

 

 

 

POTENTIAL TRANSFORMER : 11000 / 110 Volts PT,

Class 1 accuracy, 100 VA burden with HT/LT fuses. Makes: ECS / SILKANS / PRAGATHI / NARAYAN POWER TECH or EQVT - 1 No

 

 

 

 

 

Digital Voltmeter 0-15KV along with Selector switch and

protection fuses/MCB for HT metering upto 15KV on incoming side -1No

Makes: CONZERV / ELMEASURE or EQVT

 

 

 

 

 

Dual core dual ratio Current transformers with 50-300/5 amp, 15VA burden and accuracy class 1 for metering & class 5P10 for protection of makes ECS / SILKANS / PRAGATHI / NARAYAN POWER TECH -3Nos

 

 

 

 

 

0-300ADigitalTypeAmmeterwithselectorswitch-1No Makes : CONZERV / ELMEASURE orEQVT

 

 

 

 

 

Microprocessor based non directional combined 2 over current & one earth fault relay -1No

Makes: EASUN REYROLLE or equivalent

 

 

 

 

 

POWER PACK: Supply, Installation, testing and

commissioning of Power pack with 230V input and 110V DC continuous out put suitable for closing / tripping / indication of VCB with 2.5sqmm FRLS copper cable etc as required.

 

 

 

 

 

Master trip relay-1No

Makes: EASUN REYROLLE or equivalent (Makes)

 

 

 

 

 

Three element transformer fault auxilary relay - 2 Nos

Makes: EASUN REYROLLE or equivalent

 

 

 

 

 

Breaker control switch-1No

Makes: Switron or equivalent

 

 

 

 

 

Local/Remote switch-1No

Makes: Switron or equivalent

 

 

 

 

 

Indicating lamps-1set

Makes: Vaishnov or equivalent Reputed brand

 

 

 

 

 

Space heater & thermostat -2Nos

Makes: Eltek or equivalent

 

 

 

 

 

MCB's of suitable current rating - 3 Nos

 

 

 

 

 

Anti pumping relay -1No

Makes: Reputed brand with ISI mark

 

 

 

 

 

Electrionic Audio alarm system with hooter -1No

Makes : Reputed brand

 

 

 

 

 

Auxiliary plug & socket of 230VAC/10A -1No

Makes: Reputed brand with ISI mark

 

 

 

 

 

Panel illumination lamp 230V/40W -1No

Makes: Reputed brand with ISI mark

 

 

 

 

 

 

 

 

 

1454

ELEC-7.15.13

Supply,transpotation,installation,testing                                                                                          and commissioning of HT OUTDOOR type single panel switchgear with VCB of floor mounted, metal clad 11KV, 630A,notlessthan18.4KA(350MVA)VCBPanel,with1No VCBs totally enclosed and horizantal drawout type, horizontal isolation type breaker as per IS 13118 as amended upto date and additional specifications having capacities as mentioned below , single break trip free mechanism, motorised/manually charged and auto manually closing breaker suitable for use on 12KV,3phase,50HZ AC supply with self contained fully interlocked rackin and rackout mechanism air insulated allumium Busbars of 630A capacity, Breaker featured with ON/OFF indicator with hand trip device, spring reliefcoil, shunt trip coil and auxillary switch of 6NO + 6NC and equiped with following switchgears and accessories incommingconnectionssuitablefor3x95SqmmXLPE11KV Cable as required etc complete with adaptor box for outgoingtermination.

Makes: Kirloskar / Schneider / Siemens / Crompton Greaves / ABB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450000

 

 

Incoming-

 

 

 

 

 

11KV, 630A,not less than 18.40KA VCB - 1No.

 

 

 

 

 

POTENTIAL TRANSFORMER : 11000 / 110 Volts PT,

Class 1 accuracy, 100 VA burden with HT/LT fuses. Makes: ECS / SILKANS / PRAGATHI / NARAYAN POWER TECH or EQVT - 1 No

 

 

 

 

 

Digital Voltmeter 0-15KV along with Selector switch and

protection fuses/MCB for HT metering upto 15KV on incoming side - 1No

Makes: CONZERV / ELMEASURE or EQVT

 

 

 

 

 

Dual core dual ratio Current transformers with 50-300/5

amp, 15VA burden and accuracy class 1 for metering & class 5P10 for protection - 3 Nos

Makes : ECS / SILKANS / PRAGATHI / NARAYAN

POWER TECH

 

 

 

 

 

0-300ADigitalTypeAmmeterwithselectorswitch-1No Makes : CONZERV / ELMEASURE orEQVT

 

 

 

 

 

Microprocessor based non directional combined 2 over current & one earth fault relay - 1No

Makes: EASUN REYROLLE or equivalent

 

 

 

 

 

POWER PACK: Supply, Installation, testing and

commissioning of Power pack with 230V input and 110V DC continuous out put suitable for closing / tripping / indication of VCB with 2.5sqmm FRLS copper cable etc as required.

 

 

 

 

 

Master trip relay-1No

Makes: EASUN REYROLLE or equivalent (Makes)

 

 

 

 

 

Three element transformer fault auxilary relay - 2 Nos

Makes: EASUN REYROLLE or equivalent

 

 

 

 

 

Breaker control switch-1No

Makes: Switron or equivalent

 

 

 

 

 

Local/Remote switch-1No

Makes: Switron or equivalent

 

 

 

 

 

Indicating lamps-1set

Makes: Vaishnov or equivalent Reputed brand

 

 

 

 

 

Space heater & thermostat -2Nos

Makes: Eltek or equivalent

 

 

 

 

 

MCB's of suitable current rating- - 3 Nos

 

 

 

 

 

Anti pumping relay -1No

Makes: Reputed brand with ISI mark

 

 

 

 

 

Electrionic Audio alarm system with hooter -1No

Makes : Reputed brand

 

 

 

 

 

Auxiliary plug & socket of 230VAC/10A -1No

Makes: Reputed brand with ISI mark

 

 

 

 

 

Panel illumination lamp 230V/40W -1No

Makes: Reputed brand with ISI mark

 

 

 

 

 

 

 

 

 

 

7.16

L.T.      LINE      MATERIALS       AND             LIGHTENING PROTECTIONSYSTEM

 

 

 

1455

ELEC-7.16.1

Supply and erecting approved make 11KV, 5KA metal oxide lightning arrestors suitable for 11 KV supply with necessary materials on existing cross arm.

 

1

 

No

 

1400

 

ELEC-7.16.2

Supply   and erecting porcelain----------------------------------------------------------------- insulator

suitable for 11KV line with suitable hardware on existing cross arms.

 

 

 

1456

a

Disc type

1

No

530

1457

b

Pin type

1

No

270

1458

c

Post type

1

No

600

1459

ELEC-7.16.3

Supply and erecting porcelain pin/shackle type insulator suitable for L. T.

 

1

 

No

 

80

 

ELEC-7.16.4

Approved made 11KV, ----------------- A.B switch with all standard accessories etc., complete with cost and conveyance of all materials.

 

 

 

1460

a

400A

1

No

6500

1461

b

200A

1

No

5500

1462

ELEC-7.16.5

11KV, H.G fuse set including all standard accessories etc., complete with cost and conveyance of all materials.

 

1

 

No

 

3600

1463

ELEC-7.16.6

Supply of 7/3.15 AAA C all Alluminium annealed conductor Rabit.

 

1

 

Km

 

24500

1464

ELEC-7.16.7

Supply of 7/2.50 AAA C all Alluminium annealed conductor Weasel.

 

1

 

Km

 

15000

1465

ELEC-7.16.8

Supply of 9.1 Mtr PSCC Pole 280 Kg Working load.

1

No

3500

1466

ELEC-7.16.9

Supply of 8.0 Mtr PSCC Pole 140 Kg Working load.

1

No

1900

1467

ELEC-7.16.10

Supply of 175 x 85 mm / 150 x 75 mm RS Joist.

1

Kg

65

1468

ELEC-7.16.11

Supply and installation of advanced lighting protection with 205 -580mm height and 4.60 - 4.940 kgs, and having Rod length 760mm, weight 1.795 kgs with stainless steel rod, working on the principle of (ESE) Early Streamer Emission technology, having a coverage radius of 79 Mts under level 1 protection and 107 Mtrs radius under level 4 protection when mounted on 5 - 15 mts height of existing lattice tower giving level 1 protection and anticipation emission time of 60 - 72 micro seconds. The ESE should be manufacturedaccordingtostandardNFC17-102:2011and CE certified including functional integrity etc Complete. Make : EARTHPLUS (THUNDER GUARD) / NIMBUS / KALRE /FOREND.

 

 

 

 

 

 

1

 

 

 

 

 

 

No

 

 

 

 

 

 

114000

1469

ELEC-7.16.12

Installation and commissioning of advanced lighting protection systems which includes

  1. 50mm dia C class GI mast with base plate of length 5.0 Mtrs with FRP coller (Insulatingbush).
  2. Laying of CCBed
  3. Installation of LightingRod
  4. Laying of Downconductor
  5. Installation ofCounter
  6. Installation of EarthElectrodes
  7. Interconnection between theElectrodes
  8. Specialised supporting guy wire and all fitting accessories.
  9. Terminationofdownconductortoearthbusetccomplete

 

 

 

 

 

 

1

 

 

 

 

 

 

No

 

 

 

 

 

 

29200

1470

ELEC-7.16.13

Supply of electro-Mechanical counter

Makes: EARTHPLUS (THUNDER GUARD) / NIMBUS / KALRE / FOREND.

 

1

 

Pt

 

15000

1471

ELEC-7.16.14

Providingearthelectrodeoflowcarbonsteelrod,ULlisted of 17.2 mm dia, 3 Mtr long, coated with copper of 254 microns thickness, CPRI tested for short time current withstand test of 25 kA, coating thickness, environmental test (Salt Mist Test), Bend test, Tensile strength, Yield / tensile ratio, Electrical Resistivity test, complete with clamps and 2 bags of Earthplus ULTRA high grade earthing compound IEC 62561-7 complaint Eco-friendly, Maintenance free, anti corrosive, lead-free, super conductive, mineral based high-grade earthingcompound, to enhance soil conductivity. With resistance <0.20 ohms- meter, should be leach proof & sulphur free complete with earthinspectionchamberofdimensions:Width:320mmx 320 mm, Height : 192 mm, Weight : 30 Kgs, Load bearing capacity : 5000Kgs

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

Pt

 

 

 

 

 

 

 

 

10300

 

 

SECTION - 8

 

 

 

 

8.1

NET WORKING

 

 

 

 

ELEC-8.1.1

Supplyof---------------------- telephone coppercable.

Makes : Finolex / Delton / Surabi / Polycab

 

 

 

1472

a

2 Pair, 0.5mm

100

Mtrs

910

1473

b

5 Pair

100

Mtrs

2540

1474

c

10 Pair

1

Mtr

36

1475

d

20 Pair

1

Mtr

70

1476

e

50 Pair

1

Mtr

175

 

ELEC-8.1.2

Supply of --------------- Telephone distribution box with back mount frame, krone connector, powder coated metal body with lock and key arrangement.

 

 

 

1477

a

10 pair

1

No

580

1478

b

20 pair

1

No

880

1479

c

50 pair

1

No

1850

1480

d

200 pair

1

No

7000

 

ELEC-8.1.3

Supply of LAN Cable cat -

Makes : D Link / AMP / Molex / Legrand / Krone.

 

 

 

1481

a

6 UTP cable.

100

Mtrs

2100

1482

b

6 STP cable.

100

Mtrs

4000

 

ELEC-8.1.4

SupplyofCat6RJ-45informationoutletsincluding----------

-- plate.

Makes : D Link / AMP / Molex / Legrand / Krone.

 

 

 

1483

a

Duel face plate.

1

No

305

1484

b

Single face plate.

1

No

230

 

ELEC-8.1.5

Supplyof------------ managebleswitches

Makes : CISCO / Net Gear / HP / D link.

 

 

 

1485

a

48 Port

1

No

13870

1486

b

24 Port

1

No

6000

1487

c

8 Port

1

No

1100

1488

ELEC-8.1.6

Supply of access point.

Makes:CISCO-WAP321oritsequivalentinNetGear/HP

/ D link.

 

1

 

No

 

11100

 

ELEC-8.1.7

Supplyof------------ length moulded patchcord.

Makes : D Link / AMP / Molex / Legrand / Krone.

 

 

 

1489

a

7 feet

1

No

200

1490

b

3 feet

1

No

180

1491

ELEC-8.1.8

Supply of 24 port patch panels

Makes : D Link / AMP / Molex / Legrand / Krone.

 

1

 

No

 

5800

1492

ELEC-8.1.9

Supply of 100 pair MDF loaded with 2/10 Modular Makes : Krone make or its equivalent.

 

1

 

No

 

3300

1493

ELEC-8.1.10

Supply of 100 Pair raiser cable for telephone Makes : Finolex / Delton / Surabi / Polycab.

 

1

 

Mtr

 

350

 

 

RACKS - WALL MOUNT

 

 

 

 

ELEC-8.1.11

Supply of ……… wall mounting net work rack with power

spike including all accessories.

 

 

 

1494

a

6U Wall

1

No

4200

1495

b

9U wall

1

No

5000

1496

c

12U wall

1

No

5800

1497

d

15U wall

1

No

6600

 

 

RACKS - FLOOR STAND

 

 

 

 

ELEC-8.1.12

Supply  and  installation of IP 20,  IK08------------------------------------------------------------------- 600mm

Width x 800mm Deep Floor mounting net work rack with all accessories like front and rear doors, fans, castors, cable manager, shelf, power distribution unit, hardware packet. Mod cap floor stand : Modular construction of the rack madeof4vertical,4Horizontaland4depthalloyextruded multi folded hallow profiles bolted and joined together with links and corner blocks. 3 Pairs of support channelsto equatetheloadevenlyandcastorprovisionatbottomside. Painting shade : Combination of RAL 7035 / 7037 fine texture - 60 to 80 microns. or RAL 9005 fine texture - 60 to 80 microns complies with standards : UL 2416, Din 41494, IECEN60529,IECEN62262,IECEN600682-11,ISO9001-

2008.

Makes : HCL / Val / Rittal / APW.

 

 

 

1498

a

17U floor

1

No

22000

1499

b

24U floor

1

No

27000

1500

c

27U floor

1

No

30000

1501

d

32U floor

1

No

36000

1502

e

36U floor

1

No

40000

1503

f

42U floor

1

No

44000

 

ELEC-8.1.13

Supply of -------------- (Indoor / Out door), Single mode armourd, Optic fibre cable.

Makes : D Link / AMP / Molex / Legrand / Krone.

 

 

 

1504

a

6 Core

1

Mtr

70

1505

b

12 Core

1

Mtr

95

 

ELEC-8.1.14

Supply of ------------- fibre distribution unit. (FDU / LIU) loaded with couplers etc complete.

Makes : D Link / AMP / Molex / Legrand / Krone.

 

 

 

1506

a

6 port

1

No

6700

1507

b

12 port

1

No

8500

1508

ELEC-8.1.15

Supply of Subscriber connector (SC) to SC / LC patch card of 1 Mtr length.

Makes : D Link / AMP / Molex / Legrand / Krone.

 

1

 

No

 

1800

1509

ELEC-8.1.16

Supply of single mode SC / LC to SC / LC patch card of 1 Mtr length.

Makes : D Link / AMP / Molex / Legrand / Krone.

 

1

 

No

 

2000

1510

ELEC-8.1.17

Supply of single mode SC / LC to SC / LC patch card of 2 Mtr length.

Makes : D Link / AMP / Molex / Legrand / Krone.

 

1

 

No

 

2500

1511

ELEC-8.1.18

Supply of Pigtails for fibre core connectivity.

Makes : D Link / AMP / Molex / Legrand / Krone.

 

1

 

No

 

120

1512

ELEC-8.1.19

Suppy of 6 Core single mode fibre optic cable armoured.

1

Mtr

75

1513

ELEC-8.1.20

Suppy of 12 Core single mode fibre optic cable armoured.

1

Mtr

90

1514

ELEC-8.1.21

Suppy of 24 Core single mode fibre optic cable armoured.

1

Mtr

140

 

8.2

RACEWAYS AND JUNCTION BOXES

 

 

 

 

ELEC-8.2.1

Supplyof----------------------- GIRacewaysof2mmthickwith

top cover and required hard ware etc complete.

 

 

 

1515

a

100mm x 38mm

1

Mtr

450

1516

b

150mm x 38mm

1

Mtr

595

1517

c

300mm x 38mm

1

Mtr

1020

1518

d

100mm x 25mm

1

Mtr

430

1519

e

150mm x 25mm

1

Mtr

550

1520

f

300mm x 25mm

1

Mtr

990

 

ELEC-8.2.2

Supplyof........................................ G.I. Junction box of2mm

thick for direct acces to cables at the inter section of Raceways.

 

 

 

1521

a

172mm x 52mm

1

No

340

1522

b

222mm x 52mm

1

No

425

1523

c

372mm x 52mm

1

No

820

 

8.3

EPABX SYSTEM

 

 

 

 

 

SMALL SYSTEM

 

 

 

1524

ELEC-8.3.1

IPBaseddigtalTelephone(EPABX)system---------- complied

with following specifications:

  1. IP @ Core, PCM/TDM, Nonblocking,
  2. Must Support PRI, E1, AnalogJunctions
  3. Must Support PCConsole,
  4. Must support Mobile SIP (Android andIos)
  5. Must support VoiceMail
  6. Must support Card basedGSM
  7. Inbuilt 8 Channel AutoAttendant
  8. InbuiltCallDetailsSoftwarewithsearchenginesoftware
  9. 4 AnalogTrunks
  10. 6 DigitalExtensions
  11. 32 AnalogExtensions
  12. 1DigitalKeyPhonewithminimum16Keys(Mustwork only on 2wires)
  13. Expandableto64AnalogExtensionsormore

ApprovedBrands:NEC/Alcatel/Karel/Unify

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

82680

1525

ELEC-8.3.2

IPBaseddigtalTelephone(EPABX)system---------- complied

with following specifications:

  1. IP @ Core, PCM/TDM, Nonblocking,
  2. Must Support PRI, E1, AnalogJunctions
  3. Must Support PCConsole,
  4. Must support Mobile SIP (Android andIos)
  5. Must support VoiceMail
  6. Must support Card basedGSM
  7. Inbuilt 8 Channel AutoAttendant
  8. InbuiltCallDetailsSoftwarewithsearchenginesoftware
  9. 4 AnalogTrunks
  10. 6 DigitalExtensions
  11. 48 AnalogExtensions
  12. 1DigitalKeyPhonewithminimum16Keys(Mustwork only on 2wires)
  13. Expandableto64AnalogExtensionsormore

ApprovedBrands:NEC/Alcatel/Karel/Unify

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

90800

1526

ELEC-8.3.3

IPBaseddigtalTelephone(EPABX)system---------- complied

with following specifications:

  1. IP @ Core, PCM/TDM, Nonblocking,
  2. Must Support PRI, E1, AnalogJunctions
  3. Must Support PCConsole,
  4. Must support Mobile SIP (Android andIos)
  5. Must support VoiceMail
  6. Must support Card basedGSM
  7. Inbuilt 8 Channel AutoAttendant
  8. InbuiltCallDetailsSoftwarewithsearchenginesoftware
  9. 4 AnalogTrunks
  10. 1 ISDN PRIModule
  11. 6 DigitalExtensions
  12. 48 AnalogExtensions
  13. 1DigitalKeyPhonewithminimum16Keys(Mustwork only on 2wires)
  14. Expandableto64AnalogExtensionsormore

ApprovedBrands:NEC/Alcatel/Karel/Unify

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

100800

1527

ELEC-8.3.4

IPBaseddigtalTelephone(EPABX)system---------- complied

with following specifications:

  1. IP @ Core, PCM/TDM, Nonblocking,
  2. Must Support PRI, E1, AnalogJunctions
  3. Must Support PCConsole,
  4. Must support Mobile SIP (Android andIos)
  5. Must support VoiceMail
  6. Must support Card basedGSM
  7. Inbuilt 8 Channel AutoAttendant
  8. InbuiltCallDetailsSoftwarewithsearchenginesoftware
  9. 4 AnalogTrunks
  10. 6 DigitalExtensions
  11. 64 AnalogExtensions
  12. 1DigitalKeyPhonewithminimum16Keys(Mustwork only on 2wires)
  13. Expandableto64AnalogExtensionsormore

ApprovedBrands:NEC/Alcatel/Karel/Unify

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

104000

1528

ELEC-8.3.5

IPBaseddigtalTelephone(EPABX)system---------- complied

with following specifications:

  1. IP @ Core, PCM/TDM, Nonblocking,
  2. Must Support PRI, E1, AnalogJunctions
  3. Must Support PCConsole,
  4. Must support Mobile SIP (Android andIos)
  5. Must support VoiceMail
  6. Must support Card basedGSM
  7. Inbuilt 8 Channel AutoAttendant
  8. InbuiltCallDetailsSoftwarewithsearchenginesoftware
  9. 4 AnalogTrunks
  10. 1 ISDN PRIModule
  11. 6 DigitalExtensions
  12. 64 AnalogExtensions
  13. 1DigitalKeyPhonewithminimum16Keys(Mustwork only on 2wires)
  14. Expandableto64AnalogExtensionsormore

ApprovedBrands:NEC/Alcatel/Karel/Unify

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

113900

1529

ELEC-8.3.6

Analog Extension Card (with Caller ID) 8 extensions.

1

No

13900

1530

ELEC-8.3.7

Analog Extension Card (with Caller ID) 16 extensions.

1

No

18100

1531

ELEC-8.3.8

Analog Trunk Card (with Caller ID) 4 trunks.

1

No

15400

1532

ELEC-8.3.9

Analog Trunk Card (with Caller ID) 8 trunks.

1

No

19200

1533

ELEC-8.3.10

Digital Extension Card for 8 digital extensions:

1

No

17900

1534

ELEC-8.3.11

Digital Extension Card for 16 digital extensions:

1

No

30000

1535

ELEC-8.3.12

E1 Trunk Card or PRI Card

30 ISDN PRI or R2 trunk channels.

 

1

 

No

 

45000

 

8.4

LARGE SYSTEM

 

 

 

1536

ELEC-8.4.1

Supply, Installation, Testing and Commissioning of IP BaseddigtalTelephone(EPABX)system--compliedwith followingspecifications:

  1. IP @ Core, PCM/TDM switching, Nonblocking,
  2. Must Support PRI, E1, AnalogJunctions
  3. Must Support PCConsole,
  4. Must support Mobile SIP (Android andIOs)
  5. Must support VoiceMail
  6. Must support Card basedGSM
  7. InbuiltCallDetailsSoftwarewithsearchenginesoftware
  8. 8 AnalogTrunks
  9. 8 DigitalExtensions
  10. 96 AnalogExtensions
  11. 1DigitalKeyPhonewithminimum16Keys(Mustwork only on 2wires)
  12. Expandableto220Portswiredormoreatextracost

Approved Brands: NEC/ Alcatel/ Karel/ Unify

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

227300

1537

ELEC-8.4.2

Supply, Installation, Testing and Commissioning of IP BaseddigtalTelephone(EPABX)system--compliedwith followingspecifications:

  1. IP @ Core, PCM/TDM switching, Nonblocking,
  2. Must Support PRI, E1, AnalogJunctions
  3. Must Support PCConsole,
  4. Must support Mobile SIP (Android andIOs)
  5. Must support VoiceMail
  6. Must support Card basedGSM
  7. InbuiltCallDetailsSoftwarewithsearchenginesoftware
  8. 8 AnalogTrunks
  9. 1PRITrunkmodule
  10. 8 DigitalExtensions
  11. 128 AnalogExtensions
  12. 1DigitalKeyPhonewithminimum16Keys(Mustwork only on 2wires)
  13. Expandableto220Portswiredormoreatextracost

Approved Brands: NEC/ Alcatel/ Karel/ Unify